Beckhoff CX2100­00x4 Bedienungsanleitung Seite 20

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 45
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 19
Productoverview
Init
AfterswitchontheEtherCATslaveintheInitstate.Nomailboxorprocessdatacommunicationispossible.
TheEtherCATmasterinitializessyncmanagerchannels0and1formailboxcommunication.
PreOperational(PreOp)
DuringthetransitionfromInittoPreOp,theEtherCATslavecheckswhetherthemailboxhasbeencorrectly
initialized.MailboxcommunicationispossibleinthePreOpstate,butnoprocessdatacommunication.The
EtherCATmasterinitializesthesyncmanagerchannelsforprocessdata(fromsyncmanagerchannel2),the
FMMUchannelsand,iftheslavesupportsconfigurablemapping,PDOmappingorthesyncmanagerPDO
assignment.Inthisstatethesettingsfortheprocessdatatransferandperhapsterminalspecificparameters
thatmaydifferfromthedefaultsettingsarealsotransferred.
SafeOperational(SafeOp)
DuringtransitionbetweenPreOpandSafeOptheEtherCATslavecheckswhetherthesyncmanager
channelsforprocessdatacommunicationand,ifrequired,thedistributedclockssettingsarecorrect.Before
itacknowledgesthechangeofstate,theEtherCATslavecopiescurrentinputdataintotheassociatedDP
RAMareasoftheEtherCATslavecontroller(ECSC).
MailboxandprocessdatacommunicationarepossibleintheSafeOPstate;however,theslavemaintainsits
outputsinthesafestateanddoesnotoutputthem.Theinputdata,however,arealreadycyclicallyupdated.
Operational(Op)
BeforetheEtherCATmasterswitchestheEtherCATSlavefromSafeOptoOp,itmusttransmitalreadyvalid
outputdata.IntheOpstatetheslavecopiestheoutputdataofthemastertoitsoutputs.Processdataand
mailboxcommunicationispossible.
Boot
IntheBootstatetheslavefirmwarecanbeupdated.TheBootstatecanonlybereachedviatheInitstate.In
theBootstatemailboxcommunicationispossibleviatheFileAccessoverEtherCAT(FoE)protocol,butno
othermailboxcommunicationandnoprocessdatacommunicationispossible.
CX210000x420 Version1.0
Seitenansicht 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 44 45

Kommentare zu diesen Handbüchern

Keine Kommentare