Errorhandlinganddiagnostics
5 Errorhandlinganddiagnostics
5.1 DiagnosticsinthePLCprogram
Fortheanalysisoftheterminalbus(Kbus)theStateregistercanbeaccessedviaTwinCATfromaPLC
program.
Theerroranalysisispresentedasanexamplebelow.
Asignal/variableisessentiallyrequiredfortheerroranalysis:
• State(indicatesthestateofthebus:0>noerror)
ExternalvariablesmustsimilarlybecreatedinthePLCprogramforthis:
VAR
k_bus_stateAT%IB2:USINT;
END_VAR
TheerrorcanthenbedeterminedinthePLCprogramasfollows(thisispseudocode,whichisnotdirectly
executableinthisform)
....
IFk_bus_state!=0THEN(*aufdemKBusisteinFehleraufgetreten*)
IFk_bus_state.1=1THENmeldeFehler;(*Klemmenzustandsfehler*)END_IF
IFk_bus_state.2=1THENmeldeFehler;(*Prozessdatenlängeungültig*)END_IF
IFk_bus_state.8=1THENmeldeFehler;(*keinegültigenEingänge*)END_IF
IFk_bus_state.9=1THENmeldeFehler;(*K_busInputUpdateistaktiv*)END_IF
IFk_bus_state.10=1THENmeldeFehler;(*K_busOutputUpdateistaktiv*)END_IF
IFk_bus_state.11=1THENmeldeFehler;(*WatchdogFehler*)END_IF
IFk_bus_state.15=1THENmeldeFehler;(*Busistasynchron*)END_IF
END_CASE
k_bus_request:=TRUE;(*RücksetzendesBusses,wennFehlerbeseitigt,dannstartetderKlemm
buswieder*)
....
Inorderforthecontrollerandtheregisterstocooperate,theymustbelinkedintheSystemManager.