Commissioning
Name Type Description Defaultvalue
BatteryCapacity REG_DWORD RemainingUPSbatterycapacityinpercent.
Thiselementcanadoptavaluebetween0
and100(thevaluedisplayedisroundedup).
0
BatteryStatus REG_DWORD CurrentstatusoftheUPSbattery.This
elementcanadoptthefollowingvalues:
0:=thebatterystatusisunknown;
1:=thebatterystatusisOK;
2:=thebatterymustbeexchanged;
0
CommStatus REG_DWORD StatusofcommunicationwiththeUPS.This
elementcanadoptthefollowingvalues:
0:=thecommunicationwiththeUPS
hasanunknownstatus;
1:=thecommunicationwiththeUPSis
OK;
2:=thecommunicationwiththeUPS
hasbeeninterrupted.
0
FirmwareRev REG_SZ ReturnstheUPSfirmwareversionnumberas
astring.
""
SerialNumber REG_SZ ReturnstheUPSserialnumberasastring. ""
TotalUPSRuntime REG_DWORD TheremainingUPSbatterytimeinminutes. 0
UtilityPowerStatus REG_DWORD Returnsthestatusofthepowersupply.This
elementcanadoptthefollowingvalues:
0:=thestatusofthepowersupplyis
unknown;
1:=thepowersupplyisOK;
2:=apowerfailurehasbeendetected;
0
TcPowerFailCnt REG_DWORD Powerfailurecounter.Thecounterincrements
everytimeapowerfailureisdetected.
0
BatteryReplaceDate REG_SZ Dateofthelastbatterychange.Thedatecan
besetwithacommandintheBeckhoffUPS
Configurationdialog>Device
Configuration….ImplementedintheUPS
softwarev3.0.0.8andhigher.
""
TcChargeFlags REG_DWORD Batterychargeandstatusflags.Thiselement
canadoptoneormorevalues(bits)combined:
0:=unknownstatus(allbitsarezero)
1:=chargestatus"High"(bit0isset);
2:=chargestatus"Low"(bit1isset);
4:=chargestatus"Critical"(bit2isset);
8:=chargestatus"Charging"(bit3is
set);
Bit46reserved;
128:=Nobatteryconnected/found(bit7
isset);
256:=UPSfanerror(bit8isset);
Bit9isreserved;
1024:=Batterychangeintervalservice
hasexpired(bit10isset).Implemented
intheUPSsoftwarev3.0.0.8and
higher.
Bit1131reserved;
0
CX210009x464 Version1.1
Seitenansicht 63